8.2.21. Auto Clean Deice Control
This control is applicable for Heating Mode operation only and before operation starting time set by ON Timer control to improve
heating start-up operation if residual ice on outdoor heat exchanger detected.
Fifteen minutes before Standby operation, pre-deice heating operation will be performed to determine the operation decision as
shown in below figure. Auto Clean Deice operation starts to operate as soon as the pre-deice operation if all the below conditions
occur.
(a) Outdoor air temperature
0°C,
(b) Outdoor heat exchanger temperature < 0°C for 14 minutes, and
(c) Outdoor heat exchanger temperature < -8°C for 10 minutes.
The Auto Clean Deice is operated for a maximum of 12 minutes as normal Deice operation, and the period of Standby operation
is maintained including the 12-minute Auto Clean Deice operation.