16.4.25    F95 (Cooling High Pressure Abnormality) 
Malfunction Decision Conditions 
  During operation of cooling, when outdoor unit heat exchanger high temperature data (61°C) is detected by the 
outdoor pipe temperature sensor. 
 
Malfunction Caused 
  Air short circuit at indoor unit 
  Dust accumulation on the indoor unit heat exchanger 
  2/3 way valve closed 
  Faulty outdoor unit fan motor 
 Excessive refrigerant 
  Clogged expansion valve or strainer 
  Faulty outdoor pipe temperature sensor 
  Faulty outdoor unit PCB 
 
Troubleshooting