When operation stop or thermostat is off, drain pump continue operates for 6 minutes to prevent the drain water from coming
back.
9.7.3. Energy Saving
During Operation, press "Economy" button at remote control to enable Energy Saving Operation.
The air conditioner judges the stable condition, where the different between indoor suction temperature and setting temperature
is 1°C for 30 minutes and moderately shifts the set temperature in 0.5°C steps (Maximum 2°C) to control energy saving
operation.
If temperature different is out of range, energy save operation will not start.
Energy Save Operation is canceled by pressing the "Economy" button again.
9.7.4. Dew Form Prevention Control
During Cooling or Soft Dry operation, if outdoor temperature is less than 30ºC, and indoor fan speed is low or auto setting, indoor
heat exchanger temperature become lower, dew form prevention control start to prevention dew form at indoor discharge grille.
When indoor pipe temperature decrease, the cooling capacity will be reduced and the louver angle will be fixed at certain angle.
9.7.5. Freeze Prevention Control
After compressor starts operation for 4 minutes, the outdoor unit will stop its operation if indoor pipe temperature falls below 0ºC
for 6 minutes.
After 3 minutes stops, compressor restarts operation if indoor pipe temperature is 6ºC or more.
This phenomenon is to protect the indoor heat exchanger from freezing and to prevent higher volume of refrigerant in liquid from
returning to the compressor.
Energy save control time chart