9.7.6. Deice Control
During heating operation at outdoor low outdoor temperature, deice operation start timely to melt the ice formed on outdoor heat
exchanger.
During deice operation, in spite of any changes of remote control, indoor fan stop and louver angle fixed at upper side. (for louver
control: cassette and ceiling model only)
During deice operation, [DEFROST] is displayed at wired remote control (when using wireless control, POWER is blinking at
receiver of indoor unit), hot start operate after deice operation finish.
Deice operation start when accumulative heating operation time or after previous defrost end reaches 45 minutes, the outdoor
fan maintains Hi status and the outdoor heat exchanger maintains -2°C for 5 minutes.
9.7.7. Time Delay Safe Control
The compressor will not start for three minutes after stop of operation.
9.7.8. Outdoor Fan Remaining Heat Removal Control
When compressor stop, outdoor fan operates at High speed for 1 minute to remove the remaining heat.
9.7.9. Crank Case Heater Control
Crank case heater ON when the compressor is shutdown and discharge temperature is 20°C to prevents the refrigerant solving
into compressor oil inside the compressor shell at cold condition.