8.2.2.1. CS-F50DTE5 CU-L50DBE5
Heating capacity curve
Outdoor intake air ambient temperature (D.B./ °C)
-20°C-15°C-10°C-5°C0°C2°C5°C7°C10°C15°C>15°C
Heating
capacity
compensation
coefficient
0.93 0.93 0.93 0.92 0.84 0.88 0.96 1 1 1 1

Other manuals for Panasonic CS-F50DTE5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic CS-F50DTE5 and is the answer not in the manual?

Panasonic CS-F50DTE5 Specifications

General IconGeneral
Indoor unit typeCeiling
Indoor unit weight47000 g
Indoor units quantity1
Indoor unit dimensions (WxDxH)1600 x 700 x 250 mm
Indoor unit noise level (high speed)50 dB
Outdoor unit weight105000 g
Outdoor unit noise level56 dB
Outdoor unit dimensions (WxDxH)900 x 320 x 1340 mm
Hose length (max)50 m
Inverter technologyYes
Refrigerating mediumR410A
Cooling capacity (max)47700 BTU/h
Heating capacity (max)54600 BTU/h
Air conditioner functionsCooling, Heating
Cooling capacity in watts (max)14000 W
Heating capacity in watts (max)16000 W
Cooling energy efficiency (EER, W/W)2.91
Heating energy efficiency (COP, W/W)3.41