28
8.3. Safety device
8.3.1. Indoor unit
Note : Protection controlled by P.C.B installed of FM inside.
8.3.2. Outdoor unit
1MPa = 10.2kgf/cm
2
Indoor unit Heat pump model CS-F24DTE5 CS-F28DTE5 CS-F34DTE5 CS-F43DTE5 CS-F50DTE5
Cooling only model
For fan motor protection
Internal OFF °C 135 135 135 135 135
protector ON °C8787868686
For condensation temperature
protection control OFF °C5858585858
Heat exchanger RESET °C5454545454
thermistor
For P.C.B current protection
Current fuse CUT A 3.15 3.15 3.15 3.15 3.15
Outdoor unit Heat pump
model
50Hz CU-L24DBE5 CU-L28DBE5 CU-L34DBE5 CU-L43DBE5 CU-L50DBE5
For refrigerant cycle
High pressure OFF
MPa
4.2 4.2 4.2 4.2 4.15
switch ON
MPa
3.3 3.3 3.3 3.3 3.3
For compressor over current
protection for cooling mode
CT1 frequency down OFF A 12 12.6 17 20 22.5
RESET A 8 9 13 15 17.5
CT2 compressor stop OFF A 16 17 22 25 27.5
For compressor over current
protection for heating mode
CT1 frequency down OFF A 14.6 14.6 23 25 25.2
RESET A 8 9 13 15 17.5
CT2 compressor stop OFF A 18 19 28 30 30
Discharge temp protection
Discharge temperature Compressor °C
Td 110°C Comp OFF
thermistor (Td) OFF
Td 110°C x 3 times within 1 hour display error cord
Liquid compress protection
Crankcase heater - W 33 33 33 33 33
For fan motor protection
Internal OFF °C 135 135 135 135 135
protector (49F) ON °C8787878787
For condensation temperature
protection control OFF °C5858585858
Heat exchanger RESET °C5454545454
thermistor (Th)
For control protection
Fuse CUT A 6.3 6.3 6.3 6.3 6.3

Other manuals for Panasonic CS-F50DTE5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic CS-F50DTE5 and is the answer not in the manual?

Panasonic CS-F50DTE5 Specifications

General IconGeneral
Indoor unit typeCeiling
Indoor unit weight47000 g
Indoor units quantity1
Indoor unit dimensions (WxDxH)1600 x 700 x 250 mm
Indoor unit noise level (high speed)50 dB
Outdoor unit weight105000 g
Outdoor unit noise level56 dB
Outdoor unit dimensions (WxDxH)900 x 320 x 1340 mm
Hose length (max)50 m
Inverter technologyYes
Refrigerating mediumR410A
Cooling capacity (max)47700 BTU/h
Heating capacity (max)54600 BTU/h
Air conditioner functionsCooling, Heating
Cooling capacity in watts (max)14000 W
Heating capacity in watts (max)16000 W
Cooling energy efficiency (EER, W/W)2.91
Heating energy efficiency (COP, W/W)3.41

Related product manuals