9.1.2. Room Temperature Control (Compressor Control)
The room temperature is adjusted by changing the compressor´s operation frequency in response to the difference between setting
temperature of remote control unit and the room temperature (intake air temperature sensor).
9.1.2.1. Cooling Operation
·
Thermostat OFF temperature = setting temperature of
remote control - 2 °C
·
Thermostat ON temperature = setting temperature of
remote control - 2.0 °C or higher
·
Thermostat goes OFF when the intake air temperature
drops below the thermostat OFF temperature.
9.1.2.2. Dry Mode Operation
9.1.2.2.1. Dry Mode Operation (Applicable Intake Temperature: 15 °C or Higher)
·
Thermostat OFF temperature = setting temperature of
remote control - 3 °C
·
Thermostat ON temperature = setting temperature of
remote control - 3.0 °C or higher
·
Thermostat goes OFF when the intake air temperature
drops below the thermostat OFF temperature.
·
When the thermostat OFF temperature is approached, the
operation mode is switched to the dry mode operation (low-
frequency operation, SLo fan speed).
9.1.2.3. Heating Operation
·
Thermostat OFF temperature = setting temperature of
remote control + 1.0 °C
·
Thermostat ON temperature = setting temperature of
remote control + 1.0 °C or lower
·
The maximum frequency operation is approached when
operation has continued for 3 minutes at the rated
frequency operation.