12.2. OUTDOOR UNIT (CU-2E15CBPG/2E18CBPG)
Indoor/Outdoor Unit Installation Diagram
Piping direction Attention not to
bend up drain hose
Right
Right Bottom
Right Rear
Left
Rear
Left Bottom
Left
(Front side)
This illustration is for explanation purposes only.
The indoor unit will actually face a different way.
Installation parts you
should purchase ( )
10 cm
or more
10 cm
or more
100 cm
or more
30 cm
or more
Applicable piping kit
CZ-3F5, 7AEN
INDOOR UNIT
SELECT THE BEST LOCATION
OUTDOOR UNIT
1
1
2
1
No. Accessories part Qty. No. Accessories part Qty.
Attached accessories.
1
6
1
2
1
Remote control holder fixing
screw
Drain elbow
PIPE size
Max. total
Length
(m)
30
Additional
gas charge
amount
(g/m)
20
Max.
Elevation
(m)
10
Common
Length
(m)
15
Min.
Length
(m)
3m/Indoor
unit
Gas
3/8"
Note: (1)It is possible to extend the piping length of one unit up to 20 meters.
However, the total piping length must not exceed 30 meters.
(2)If the piping length exceeds 20 meters, refrigerant of 20g per meter
must be added.
Liquid
1/4"
Connecting cable
4 x 1.5 mm
2
or more.
Type designation 245 IEC 57
(H05RN-F)
1
2
3
4
5
6
7
8
9
Installation plate
Installation plate fixing
screw
Remote control
Battery
Air purifying filter
Solar refreshing
deodorizing filter
Remote control
holder
Attaching the remote control holder to the wall
Remote control holder
fixing s crewsıı
Remote control
holder
Remote
control
(Left and right are identical)
Insulation of piping connections
Carry out insulation
after checking for gas
leaks and secure with
vinyl tape.
Power supply cable:
3 X 1.5mm
2
or more.
Type designation 245 ICE
57(H05RN-F)
( ) Vinyl tape
8
3
7
15A
Breaker
50Hz
230V
~
1
Installation plate
5 cm
or more
5 cm
or more
There should not be any heat source or steam near
the unit.
There should not be any obstacles blocking the air
circulation.
A place where air circulation in the room is good.
A place where drainage can be easily done.
A place where noise prevention is taken into
consideration.
Do not install the unit near the door way.
Ensure the spaces indicated by arrows from the wall,
ceiling, fence or other obstacles.
Recommended installation height for indoor unit shall
be at least 2.3 m.
If an awning is built over the unit to prevent direct
sunlight or rain, be careful that heat radiation from the
condenser is not obstructed.
There should not be any animal or plant which could be
affected by hot air discharged.
Keep the spaces indicated by arrows from wall,ceiling,
fence or other obstacles.
Do not place any obstacles which may cause a short
circuit of the discharged air.
If piping length is over the common length, additional
refrigerant should be added as shown in the table.
Sleeve ( )
Saddle ( )
Additional drain hose ( )
3/8" Gas side piping ( )
1/4" Liquid side piping ( )
Bushing Sleeve ( )
Putty (Gum type sealer) ( )
Bend the pipe as closely
on the wall as possible,
but be careful that it
doesnt break.
5
6
Air purifying filter
or
Solar refreshing
deodorizing filter
Vinyl tape (Wide) ( )
Apply after carrying out a
drainage test.
To carry out the
drainage test, remove
the air filters and pour
water into the heat
exchanger.
70
CS-ME7CKPG / CS-ME10CKPG / CS-ME12CKPG / CS-ME14CKPG / CS-ME18CKPG / CU-2E15CBPG / CU-2E18CBPG / CU-3E23CBPG / CU-4E27CBPG

Table of Contents

Other manuals for Panasonic CS-ME12CKPG

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic CS-ME12CKPG and is the answer not in the manual?

Panasonic CS-ME12CKPG Specifications

General IconGeneral
BrandPanasonic
ModelCS-ME12CKPG
CategoryAir Conditioner
LanguageEnglish

Related product manuals