9.1.4.1. Cooling Operation
1. Automatic fan speed
This air conditioner comes with a odour removing function. When operation starts or the thermostat is set ON, the fan stops for
40 seconds. This is done in order to clean off the odour components which have accumulated on the heat exchanger using the
moisture produced by dehumidification.
2. Maximum cooling capacity
When, in order to lower the room temperature quickly for the high cooling load, the fan speed is set to high and the temperature
setting is 16 °C, the fan speed is boosted for the first 30 minutes after operation is commenced. (Fan speed will be shifted to
"SHi".)
3. Anti-dew formation control
When the anti-dew formation control is activated, the fan speed is lowered. (In door fan speed approaches the "Me".)
4. Anti-freezing control
When the temperature of the indoor unit heat exchanger drops to below 12 °C, the compressor speed is adjusted. When it
exceeds 14 °C, operation returned to normal.
5. Powerful mode operation control
At the automatic fan speed setting, operation is transferred to the automatic powerful fan speed setting. At the manual fan
speed setting, the fan speed is boosted by two steps.
6. Quiet mode operation control
At the automatic fan speed setting, operation is transferred to the automatic quiet mode fan speed setting. At the manual fan
speed setting, the fan speed is reduced by one step.
7. Forced cooling operation
When AUTO button of the indoor unit is pressed for 5 seconds, the forced cooling operation is started with high fan speed.
8. Auto operation
Operation is performed at the automatic fan speed when operation is initiated using the auto operation button or when a cooling
operation has been initiated using the remote control when a diagnostic display for the kind of trouble by which auto operation
is enabled has appeared.
28
CS-ME7CKPG / CS-ME10CKPG / CS-ME12CKPG / CS-ME14CKPG / CS-ME18CKPG / CU-2E15CBPG / CU-2E18CBPG / CU-3E23CBPG / CU-4E27CBPG