When the operation mode is changed over, the value for t1, t2 and t3 are shifted as follows:
Cooling/Soft dry → Heating: -2 °C
Heating → Cooling/Soft dry: +2 °C
·
When the indoor intake air temperature is lower than 16 °C, heating operation is immediately started.
·
When the outdoor air temperature is more than 25 °C, and the intake air temperature is over 16 °C, cooling operation is
immediately started.
·
The operation mode is judged every 3 hours.
9.1.5.2. Temperature Shift
·
When the operation mode (Heating, Cooling or Soft Dry) is decided, the internal setting temperature will shift as shown below:
9.1.6. Sleep Timer / Sleep Operation Mode
·
When the sleep timer is set using the remote control, the air conditioner will stop after the set time (1, 2, 3, 5 or 7 hours) has
elapsed.
Remaining time of the remote control unit is displayed in 1-hour increments. When the set time is reached, the remaining time
display is cleared.
·
When the sleep timer is set to 5 or 7 hours, sleep mode operation is activated after 3 hours.
·
When the sleep mode operation is activated, the compressor operation frequency and outdoor fan speed are reduced to quiet
down the noise of the outdoor unit.
1. Sleep mode operation during cooling and dry operation
31