12.5 Low Pressure Prevention Control (Gas Leakage Detection)
• Control start conditions
o For 5 minutes, the compressor continuously operates and outdoor total current is between 0.78A and 1.15A.
o During Cooling and Dry operation:
Indoor suction temperature – indoor piping temperature is below 4°C
• Control contents
o Compressor stops (and restart after 3 minutes).
o If the conditions above happened 4 times within 60 minutes, the unit will:
· Stop operation
12.6 Compressor Tank Temperature Rise Protection Control
• Control start conditions
o For 5 minutes, the compressor continuously operates and outdoor total current is between 0.78A and 1.15A.
o During Cooling and Dry operation:
Indoor suction temperature -indoor piping temperature is below 4°C.
Indoor temperature and outdoor temperature is 30±5°C.
Remote Control setting 16°C and Hi Fan Speed.
• Control contents
o Compressor stops (and restart after 3 minutes)
o If the conditions above happened 4 times within 60 minutes, the unit will:
Stop operation
12.7 Outdoor Air Temperature Control
• The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the
diagram below.
• This control will begin 1 minute after the compressor starts.
• Compressor frequency will adjust based on outdoor air temperature.
Free
Limited Frequency
Outdoor air temperature
38°C
37°C
·
·
·
·