EasyManua.ls Logo

Panasonic CS-PS9JKT

Panasonic CS-PS9JKT
79 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
46
14.4.3 H14 (Indoor Intake Air Temperature Sensor Abnormality)
Malfunction Decision Conditions
During startup and operation of cooling and heating, the temperatures detected by the indoor intake air
temperature sensor are used to determine sensor errors.
Malfunction Caused
Faulty connector connection.
Faulty sensor.
Faulty PCB.
Troubleshooting
Sensor (Thermistor)
Characteristics
70
60
50
Resistance (k)
Temperature (ºC)
40
30
20
10
-10 0 10 20 30 40 50
0
1 Pipe temp. Sensor
2 Intake Air Temp. Sensor
1
2
When abnormality indication starts again
Check the indoor intake air temperature sensor:
Plug out connector from the indoor unit PCB
Measure the resistance of the indoor intake air
temperature sensor
For safety reason and to prevent component
breakdown, always switch off the power
before remove and connect the component.
Is the measured resistance of the indoor intake air
temperature sensor matches the value specified in its
characteristic chart?
Defect in indoor intake air temperature sensor
Replace the indoor intake air temperature
sensor
Defect in indoor unit PCB
Replace the indoor unit PCB
Check the connector connection:
Turn off the power
Check the connector connection
Is the connector connection normal?
YES
Connector poor contact
Correct the connection
NO
NO
YES

Table of Contents

Related product manuals