14.4.14 H99 (Indoor Freeze Prevention Protection: Cooling or Soft Dry)
Malfunction Decision Conditions
• Freeze prevention control takes place (when indoor pipe temperature is lower than 2°C)
Malfunction Caused
• Clogged air filter of the indoor unit
• Dust accumulation on the indoor unit heat exchanger
• Air short circuit
• Detection error due to faulty indoor pipe temperature sensor
• Detection error due to faulty indoor unit PCB
Troubleshooting
When abnormality indication starts again
Is the air filter dirt
Clean the air filter
Check the air filter
Is the indoor unit heat exchanger dirty?
• Clean the indoor unit heat
exchanger
Is there any short circuit?
Check the air
Provide sufficient air passage
NO
Does it conform to the sensor characteristic chart?
Check the indoor heat exchanger temperature
sensor
Replace the indoor unit PCB
• Defect in indoor unit PCB
• Replace the indoor unit PCB
Check the dust accumulation on the indoor unit heat
exchanger
NO
NO
YES
YES
YES
NO