14.4.16 F90 (Power Factor Correction Protection)
Malfunction Decision Conditions
During startup and operation of cooling and heating, when Power Factor Correction (PFC) protection circuitry at
the outdoor unit main PCB senses abnormal high DC voltage level.
Malfunction Caused
DC voltage peak due to power supply surge.
DC voltage peak due to compressor windings not uniform.
Faulty outdoor PCB.
Troubleshooting
YES
When abnormality indication starts again
Su
pp
l
y
volta
g
e as s
p
ecified?
YES
(~28Vdc)
Correct the power supply
Is the DC voltage between P (+) and N (-) terminal normal
between 285~315Vdc)?
Check the su
pp
l
y
volta
g
e
Operate the system. Verify PFC abnormality by measuring DC
voltage between P (+) and N (-) terminal at the outdoor unit PCB.
A
re the com
p
ressor’s windin
g
resistance
(
U-V
,
V-W
,
W-U
)
Check the compressor winding resistance:
Turn off the power supply and disconnect the harness U, V
and W .
Measure the windin
g
resistance between U-V
,
V-W and W-U
Replace the compressor
NO
Defect in PFC circuitry
Replace the outdoor unit PCB
NO
NO
YES
Replace the outdoor unit PCB.
For safety reason and to prevent
component breakdown, always
switch off the power before remove
and connect the component.