14.4.22 F98 (Input Over Current Detection)
Malfunction Decision Conditions
During cooling and heating operation, when an input over-current (16.8A) is detected by checking the input current
value being detected by current transformer (CT) with the compressor running.
Malfunction Caused
Over-current due to compressor failure.
Over-current due to defective outdoor unit PCB.
Over-current due to defective inverter main circuit electrolytic capacitor.
Over-current due to excessive refrigerant.
Troubleshooting
Turn off power supply. Check the main
circuit electrolytic capacitor.
When F98 indication ha
pp
ens
For safety reason and to prevent component
breakdown, always switch off the power
before remove and connect the component.
Get restarted and measure the input
current.
NO
Is In
p
ut current > 16.8A?
Replace the outdoor unit PCB.
NO
YES
Normal?
Check refrigerant amount.
Repair the pipe flare or union nuts.
Reclaim and recharge refrigerant.
Reclaim and recharge with correct
amount of refri
g
erant.
Excess refrigerant?
YES
NO
YES
NO
Replace outdoor unit PCB
Repl
ace outdoor unit compressor