8.5.5. Compressor Reverse Rotation Protection Control
If the compressor is operating continuously for 5 minutes or longer and the temperature difference between intake air and
indoor heat exchanger is 2.5°C or less for continuous 2 minutes, compressor will stop and restart automatically.
Time Delay Safety Control is activated before the compressor restart.
T = Intake air temperature - Indoor heat exchanger temperature
This is to prevent compressor from rotate reversely when there is an instantaneous power failure.
8.5.6. Starting Current Control
When the compressor, outdoor fan motor and indoor fan motor are simultaneously started, the indoor fan motor will start to
operate at 1.6 second later.
The reason of the difference is to reduce the starting current flow.
8.5.7. Anti-Dew Formation Control
Purpose is to prevent dew formation on indoor unit air discharge area.
The following conditions occur for 30 minutes continuously, anti-dew formation will activate:
Remote Control setting temperature is less than 25°C.
Compressor is on.
Cooling operation mode.
Indoor fan motor operate at low fan speed.
This control is cancelled immediately when above condition is changed.
Anti-Dew formation is control by:
1. Lo fan speed
Lo fan is changed to Lo+ fan
18
CS-PW18DKE CU-PW18DKE

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic CS-PW18DKE and is the answer not in the manual?

Panasonic CS-PW18DKE Specifications

General IconGeneral
BrandPanasonic
ModelCS-PW18DKE
CategoryAir Conditioner
LanguageEnglish

Related product manuals