2.3. Outdoor Unit
To protect compressor from reverse
rotation when there is an instantaneous
power failure.
60 Secs. Forced Operation Control
Once the compressor is activated, it
does not stop within the first 60 secs.
However, it stops immediately with
remote control stop signal.
Overload Protector
Inner protector.
Compressor Reverse Rotation
Protection Control
Outdoor Fan Operation Control
6-pole induction motor.
For Over-heating Protection, the Fan is
switched ON or OFF depending on the
piping temperature and the outdoor
temperature.
Deice Control
To prevent frosting at outdoor heat
exchanger during Heating Operation.
4-Way Valve Control
When the unit is switched to OFF
during Heating Operation, 4-way valve
stays at Heating position for 5 minutes.
CS-PW18DKE CU-PW18DKE
5