EasyManua.ls Logo

Panasonic CS-PW18DKE - Outdoor Unit

Panasonic CS-PW18DKE
76 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2.3. Outdoor Unit
• To protect compressor from reverse
rotation when there is an instantaneous
power failure.
60 Secs. Forced Operation Control
• Once the compressor is activated, it
does not stop within the first 60 secs.
However, it stops immediately with
remote control stop signal.
Overload Protector
• Inner protector.
Compressor Reverse Rotation
Protection Control
Outdoor Fan Operation Control
• 6-pole induction motor.
• For Over-heating Protection, the Fan is
switched ON or OFF depending on the
piping temperature and the outdoor
temperature.
Deice Control
• To prevent frosting at outdoor heat
exchanger during Heating Operation.
4-Way Valve Control
• When the unit is switched to “OFF”
during Heating Operation, 4-way valve
stays at Heating position for 5 minutes.
CS-PW18DKE CU-PW18DKE
5

Table of Contents