8.5.12. Hot Start Control
•
Hot Start Control is to prevent cool air discharge into the room when heating operation start.
•
When Heating operation starts, Indoor fan will not start until the indoor heat exchanger reaches 30°C as diagram shown.
•
Hot start is completed when indoor heat exchanger rises to 42°C or operation over 4 minutes.
8.5.13. Anti Cold Draft Control
8.5.14. Deicing Control
Deice starts to prevent frosting at outdoor heat exchanger.
•
Normal Deicing
Deice operation detection commences in Heating operation starts or 60 minutes after previous deice operation. If the
outdoor piping temperature drops to -4°C for 50 sec. continuously during compressor is in operation, deice will start.
(There is no detection during Outdoor Fan stops.)
•
Overload Deicing
During heating operation, if the outdoor Fan OFF duration (due to overload control) is accumulated up to 60 minutes and
after compressor starts for 1 minutes, deicing starts.
•
Deicing ends when
(a) 12 minutes after deicing operation starts;
(b) The outdoor piping temperature rises to about 12°C.
•
After deicing operation, compressor stops for 30 seconds and 4-way valve stays at cooling position for 10 seconds.
20