8.5.12. Hot Start Control
Hot Start Control is to prevent cool air discharge into the room when heating operation start.
When Heating operation starts, Indoor fan will not start until the indoor heat exchanger reaches 30°C as diagram shown.
Hot start is completed when indoor heat exchanger rises to 42°C or operation over 4 minutes.
8.5.13. Anti Cold Draft Control
8.5.14. Deicing Control
Deice starts to prevent frosting at outdoor heat exchanger.
Normal Deicing
Deice operation detection commences in Heating operation starts or 60 minutes after previous deice operation. If the
outdoor piping temperature drops to -4°C for 50 sec. continuously during compressor is in operation, deice will start.
(There is no detection during Outdoor Fan stops.)
Overload Deicing
During heating operation, if the outdoor Fan OFF duration (due to overload control) is accumulated up to 60 minutes and
after compressor starts for 1 minutes, deicing starts.
Deicing ends when
(a) 12 minutes after deicing operation starts;
(b) The outdoor piping temperature rises to about 12°C.
After deicing operation, compressor stops for 30 seconds and 4-way valve stays at cooling position for 10 seconds.