15.5.23. F98 (Input Over Current Detection)
Malfunction Decision Conditions
During operation of cooling and heating, when an input over-current (16.8A) is detected by checking the input current value
being detected by current transformer (CT) with the compressor running.
Malfunction Caused
Over-current due to compressor failure.
Over-current due to defective outdoor unit PCB.
Over-current due to defective inverter main circuit electrolytic capacitor.
Over-current due to excessive refrigerant.