50
15.4 Error Codes Table
Diagnosis
display
Abnormality / Protection control Abnormality Judgment
Emergency
Operation
Primary location to verify
H00 No abnormality detected - Normal operation -
H11 Indoor / Outdoor abnormal
communication
> 1 min after starting
operation
Indoor fan operation
only
Internal / external cable connections
Indoor / Outdoor PCB
H14 Indoor intake air temperature sensor
abnormality
Continue for 5 sec. -
Intake air temperature sensor
(defective or disconnected)
H15 Outdoor compressor temperature sensor
abnormality
Continue for 5 sec. -
Compressor temperature sensor
(defective or disconnected)
H16 Outdoor Current Transformer open circuit - -
Outdoor PCB
IPM (Power transistor) module
H19 Indoor fan motor mechanism lock - -
Indoor PCB
Fan motor
H23 Indoor heat exchanger temperature
sensor abnormality
Continue for 5 sec. O
(Cooling only)
Heat exchanger temperature sensor
(defective or disconnected)
H27 Outdoor air temperature sensor
abnormality
Continue for 5 sec. O
Outdoor temperature sensor
(defective or disconnected)
H28 Outdoor heat exchanger temperature
sensor abnormality
Continue for 5 sec. O
Outdoor heat exchanger
temperature sensor (defective or
disconnected)
H30 Discharge temperature sensor
abnormality
Continue for 5 sec. -
Discharge temperature sensor
H33 Indoor / Outdoor wrong connection - -
Indoor / Outdoor supply voltage
H38 Indoor / Outdoor mismatch (brand code) - - -
H97 Outdoor Fan Motor lock abnormality - -
Outdoor PCB
Outdoor Fan Motor
H98 Indoor high pressure protection - -
Air filter dirty
Air circulation short circuit
H99 Indoor heat exchanger anti-freezing
protection
- -
Insufficient refrigerant
Air filter dirty
F11 Cooling / Heating cycle changeover
abnormality
4 times occurrence within
30 minutes
-
4-way valve
V-coil
F90 PFC control 4 times occurrence within
10 minutes
-
Voltage at PFC
F91 Refrigeration cycle abnormality 7 times occurrence
continuously
-
No refrigerant
( 3-way valve is closed)
F93 Outdoor compressor abnormal revolution 4 times occurrence within
20 minutes
-
Outdoor compressor
F95 Cool high pressure protection 4 times occurrence within
20 minutes
-
Outdoor refrigerant circuit
F96 IPM (power transistor) overheating
protection
- -
Excess refrigerant
Improper heat radiation
IPM (Power transistor)
F97 Outdoor compressor overheating
protection
4 times occurrence within
20 minutes
-
Insufficient refrigerant
Compressor
F98 Total running current protection 3 times occurrence within
20 minutes
-
Excess refrigerant
Improper heat radiation
F99 Outdoor Direct Current (DC) peak
detection
7 times occurrence
continuously
-
Outdoor PCB
IPM (Power transistor)
Compressor
Note:
“O” – Frequency measured and fan speed fixed
The memory data of error code is erased when the power supply is cut off, or press the Auto Switch until “beep”
sound heard following by pressing the “CHECK: button at remote control.
Although operation forced to stop when abnormality detected, emergency operation is possible for certain errors
(refer to Error Codes Table) by using Remote Control or Auto Switch at indoor unit. However, the Remote Control
signal receiving sound is changed from one “beep” to four “beep” sounds.