16. Protection Control
16.1 Protection Control for All Operations
16.1.1 Restart Control (Time Delay Safety Control)
The Compressor will not turn on within 3 minutes from the moment operation stops, although the unit is turned on
again by pressing OFF/ON button at remote control within this period.
This control is not applicable if the power supply is cut off and on again.
This phenomenon is to balance the pressure inside the refrigerant cycle.
16.1.2 Total Running Current
1 When the outdoor unit total running current (AC) exceeds X value, the frequency instructed for compressor
operation will be decreased.
2 If the running current does not exceed X value for 5 seconds, the frequency instructed will be increased.
3 However, if total outdoor unit running current exceeds Y value, compressor will be stopped immediately for
3 minutes.
Model TZ20ZKE
TZ25ZKE/
RZ25ZKE
TZ35ZKE/
RZ35ZKE
TZ42ZKE
TZ50ZKE/
RZ50ZKE
TZ60ZKE TZ71ZKE
Operation Mode X (A) Y (A) X (A) Y (A) X (A) Y (A) X (A) Y (A) X (A) Y (A) X (A) Y (A) X (A) Y (A)
Cooling / Soft Dry (A) 3.81
15.03
4.77
15.03
6.23
15.03
7.40
15.03
10.41
14.66
10.41
14.66
13.67
19.01
Cooling / Soft Dry (B) 3.30 4.33 5.72 6.82 9.87 9.87 11.77
Heating 4.11 4.69 5.57 8.21 10.05 9.32 12.22
4 The first 30 minutes of cooling operation, (A) will be applied.
16.1.3 IPM (Power transistor) Prevention Control
Overheating Prevention Control
1 When the IPM temperature rises to 120°C, compressor operation will stop immediately.
2 Compressor operation restarts after 3 minutes the temperature decreases to 110°C.
3 If this condition repeats continuously 4 times within 20 minutes, timer LED will be blinking (“F96” is indicated).
DC Peak Current Control
1 When electric current to IPM exceeds set value, the compressor will stop operate.
2 If the set value is exceeded again more than 30 seconds after the compressor starts, the operation will
restart after 3 minutes.
3 If the set value exceeded again within 30 seconds after the compressor starts, the operation will restart after
1 minute. If this condition repeats continuously for 7 times, all indoor and outdoor relays will be cut off, timer
LED will be blinking (“F99” is indicated).
16.1.4 Compressor Overheating Prevention Control
Instructed frequency for compressor operation will be regulated by compressor temperature. The changes of
frequency are as below.
If compressor temperature exceeds 103°C, compressor will be stopped, occurs 4 times per 20 minutes, timer
LED will be blinking. (“F97” is indicated.)
39°C
38°C
(B)
(A)
Outdoor air temperature