103 
17.2  Heat Mode Performance Data 
Unit setting: Standard piping length, Hi Fan, Heat mode at 30°C 
Voltage: 230V 
17.2.1  CS-PE9RKE/CU-PE9RKE  CS-UE9RKE/CU-UE9RKE 
Indoor (°C)  Outdoor WB (°C) 
DB 
-10  -7  2  7  12 
TC  IP  TC  IP  TC  IP  TC  IP  TC  IP 
24  1803  1079  2488  1124  2772  1060  3181  867  3454  893 
20  1900  1064  2660  1120  2970  1040  3300  860  3651  873 
16  1534  1038  2733  1108  3084  1049  3400  883  3561  858 
 
17.2.2  CS-PE12RKE/CU-PE12RKE  CS-UE12RKE/CU-UE12RKE 
Indoor (°C)  Outdoor WB (°C) 
DB 
-10  -7  2  7  12 
TC  IP  TC  IP  TC  IP  TC  IP  TC  IP 
24  2278  1358  2993  1415  3381  1325  3775  1109  4099  1142 
20  2400  1340  3200  1410  3700  1300  4000  1100  4333  1117 
16  1937  1307  3288  1395  3762  1311  4035  1129  4227  1098 
 
17.2.3  CS-UE18RKE/CU-UE18RKE 
Indoor (°C)  Outdoor WB (°C) 
DB 
-10  -7  2  7  12 
TC  IP  TC  IP  TC  IP  TC  IP  TC  IP 
24  3886  2060  4775  2172  5500  2128  5261  1554  5790  1656 
20  4000  1986  4790  2090  5580  2040  5400  1470  6021  1589 
16  3735  1897  4832  1998  5640  1954  5534  1390  6182  1505 
 
TC     - Total Cooling Capacity (W) 
SHC  - Sensible Heat Capacity (W) 
IP      - Input Power (W)