12.6  Random Auto Restart Control 
  When the power supply is cut off during the operation of air conditioner, the compressor will re-operate within 
three to four minutes (there are 10 patterns between 2 minutes 58 seconds and 3 minutes 52 seconds to be 
selected randomly) after power supply resumes. 
  This type of control is not applicable during ON/OFF Timer setting. 
  This control can be omitted by open the circuit of JP1 at indoor unit printed circuit board. 
 
12.7   Indication Panel 
 
LED  POWER  TIMER  POWERFUL  QUIET 
Color  Green  Orange  Orange  Orange 
Light ON  Operation ON  Timer Setting ON  Powerful ON  Quiet ON 
Light OFF  Operation OFF  Timer Setting OFF  Powerful OFF  Quiet OFF 
 
Note: 
  If POWER LED is blinking, the possible operation of the unit are Hot Start, during Deice operation, operation 
mode judgment, or ON timer sampling. 
  If Timer LED is blinking, there is an abnormality operation occurs. 
 
12.8  Quiet Operation (Cooling Mode/Cooling Area of Dry Mode) 
A. Purpose 
To provide quiet cooling operation compare to normal operation. 
 
B. Control condition 
a.  Quiet operation start condition 
o  When “POWERFUL/QUIET” button at remote control is pressed twice. 
QUIET LED illuminates (low intensity). 
 
b.  Quiet operation stop condition 
1  When one of the following conditions is satisfied, quiet operation stops: 
a.  POWERFUL/QUIET button is pressed again. 
b.  Stop by OFF/ON switch. 
c.  Timer “off” activates. 
2  When quiet operation is stopped, operation is shifted to normal operation with previous setting. 
3  When fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed. 
4  When operation mode is changed, quiet operation is shifted to quiet operation of the new mode. 
5  During quiet operation, if timer “on” activates, quiet operation maintains. 
6  After off, when on back, quiet operation is not memorized. 
 
C. Control contents 
1  Fan speed is changed from normal setting to quiet setting of respective fan speed. 
2  Fan speed for quiet operation is reduced from setting fan speed.