The mode judging temperature and standard setting temperature can be increased by 2°C, by open the circuit of JX1 at indoor
electronic controller.
8.6. Powerful Mode Operation
•
• •
•
Purpose of this operation is to obtain the setting temperature quickly.
•
• •
•
When the Powerful Mode is set, the set temperature will be automatically decreased 3°C against the present setting
temperature (Lower temperature: 16°C).
•
• •
•
This operation automatically will be running under SHi Fan Speed (Cooling), Lo- Fan Speed (Soft Dry).
•
• •
•
Vertical Airflow Direction:-
- In “Manual” setting, the vane will automatically shift down 10° lower than previous setting.
- In “Auto” setting, the vane will automatically swing up and down. However the lower limit will be shifted 10° downward.
•
• •
•
Powerful Mode will operate for 15 minutes only, after that it will shift back to previous operation mode.
•
• •
•
Powerful Mode will stop if:-
- Powerful mode button is pressed again.
- Stopped by ON / OFF switch.
- Timer OFF activates.
- Quiet mode button is pressed.
- Operation mode button is changed.
8.7. Random Auto Restart Control
•
• •
•
If there is a power failure during air conditioners operation, operation will be automatically restarted after 3 to 4 minutes when
the power is resumed.
It will start with previous operation mode and airflow direction.
•
• •
•
Restart time is decided randomly using 4 parameter:-
Intake air temperature, setting temperature, fan speed and Air Swing Blade position.
•
• •
•
Auto Restart Control is not available when Timer is set.
•
• •
•
This control can be omitted by open the circuit of JX2. (Refer Circuit Diagram)