8.2.2.4. Anti-Dew Formation Control
Anti-Dew control is perform if the following conditions is fulfilled during cooling/dry operation.
a. Control Start Condition
1) Indoor Intake Air Temperature 24°C & above
2) Outdoor Air Temperature Refer below
3) Remote Control Setting Temperature 16°C & above, below 30°C
4) Fan tab Refer below
Control start after 1) ~ 4) continued for more than 1 minutes.
b. Control Contents
* If the outdoor temperature 30°C
Me & above (include auto air flow)
XE9DK XE12DK
0min T 30 min 47 67
30 min T 90 min 39 52
90 min T 420 min 39 52
Below Me
XE9DK XE12DK
0min T 30 min 33 44
30 min T 90 min 26 36
90 min T 420 min 26 36
* If the outdoor temperature 30°C
Me & above (include auto air flow)
XE9DK XE12DK
0min T 30 min 47 67
30 min T 90 min 39 52
90 min T 420 min 39 52
Below Me
XE9DK XE12DK
0min T 30 min 33 44
30 min T 90 min 26 36
90 min T 420 min 26 36
c. Cancellation Condition
Perform cancellation within 420 minutes after start and return to initial control.
When changing the remote control setting temperature or air flow setting during the Anti-Dew control operation.
If the above starting condition is not fulfilled.
34
CS-XE9DKE CU-XE9DKE / CS-XE12DKE CU-XE12DKE