EasyManua.ls Logo

Panasonic CS-Z35UD3RAW - Page 22

Panasonic CS-Z35UD3RAW
169 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
22
Indoor
Model CS-Z60UD3RAW
POS (EAN) 5025232886944
Outdoor
Model CU-Z60UBRA
POS (EAN) 5025232886999
Stacking No. (CS / CU / CZ) Actual Stacking Quantity (14 / 4 / – )
Piping
Pipe Diameter (Liquid / Gas) mm (inch) 6.35 (1/4) / 12.70 (1/2)
Standard length m (ft) 5.0 (16.4)
Length range (min – max) m (ft) 3 (9.8) ~ 30 (98.4)
I/D & O/D Height different m (ft) 20 (65.6)
Additional Gas Amount g/m (oz/ft) 15 (0.2)
Length for Additional Gas m (ft) 7.5 (24.6)
Drain Hose
Inner Diameter mm 16
Length mm 117.5
Indoor Heat
Exchanger
Fin Material Aluminium (Pre Coat)
Fin Type Slit Fin
Row × Stage × FPI 3 × 12 × 18
Size (W × H × L) mm 590 × 282 × 38.1
Outdoor
Heat
Exchanger
Fin Material Aluminium (Blue Coat)
Fin Type Corrugated Fin
Row × Stage × FPI 2 × 31 × 19
Size (W × H × L) mm 36.4 × 651 × 904.5:874.5
Air Filter
Material
Type
Power Supply Outdoor
Power Supply Cord A Nil
Thermostat Electronic Contol
Protection Device Electronic Contol
Dry Bulb Wet Bulb
Indoor
Operation
Range
Cooling
Maximum °C 32 23
Minimum °C 16 11
Heating
Maximum °C 30
Minimum °C 16
Outdoor
Operation
Range
Cooling
Maximum °C 46 26
Minimum °C -10
Heating
Maximum °C 24 18
Minimum °C -15 -16
1. Cooling capacities are based on indoor temperature of 27°C Dry Bulb (80.6°F Dry Bulb), 19.0°C Wet Bulb (66.2°F Wet Bulb) and outdoor air
temperature of 35°C DRY BULB (95°F Dry Bulb), 24°C Wet Bulb (75.2°F Wet Bulb).
2. Heating capacities are based on indoor temperature of 20°C Dry Bulb (68°F Dry Bulb) and outdoor air temperature of 7°C Dry Bulb (44.6°F
Dry Bulb), 6°C Wet Bulb (42.8°F Wet Bulb).
3. Specifications are subjected to change without prior notice for further improvement.

Table of Contents

Related product manuals