Indoor CS-Z25UD3EAW CS-Z35UD3EAW
Outdoor CU-Z25UBEA CU-Z35UBEA
Weight Net (I/D / O/D) kg (lb) 19 (42) / 33 (73) 19 (42) / 35 (77)
Piping
Pipe Diameter (Liquid / Gas) mm (inch) 6.35 (1/4) / 9.52 (3/8) 6.35 (1/4) / 9.52 (3/8)
Standard length m (ft) 5.0 (16.4) 5.0 (16.4)
Length range (min – max) m (ft) 3 (9.8) ~ 20 (65.6) 3 (9.8) ~ 20 (65.6)
I/D & O/D Height different m (ft) 15.0 (49.2) 15.0 (49.2)
Additional Gas Amount g/m (oz/ft) 10 (0.1) 10 (0.1)
Length for Additional Gas m (ft) 7.5 (24.6) 7.5 (24.6)
Drain Hose
Inner Diameter mm 16 16
Length mm 117.5 117.5
Indoor Heat
Exchanger
Fin Material Aluminium (Pre Coat) Aluminium (Pre Coat)
Fin Type Slit Fin Slit Fin
Row × Stage × FPI 3 × 12 × 18 3 × 12 × 18
Size (W × H × L) mm 590 × 282 × 38.1 590 × 282 × 38.1
Outdoor
Heat
Exchanger
Fin Material Aluminium Aluminium
Fin Type Corrugated Fin Corrugated Fin
Row × Stage × FPI 2 × 24 × 19 2 × 28 × 17
Size (W × H × L) mm 36.4 × 504 × 824.2:793.7 36.38 × 588 × 856.3:827.7
Air Filter
Material
Type
Power Supply Outdoor Outdoor
Power Supply Cord A Nil Nil
Thermostat Electronic Contol Electronic Contol
Protection Device Electronic Contol Electronic Contol
Dry Bulb Wet Bulb Dry Bulb Wet Bulb
Indoor
Operation
Range
Cooling
Maximum °C 32 23 32 23
Minimum °C 16 11 16 11
Heating
Maximum °C 30 – 30 –
Minimum °C 16 – 16 –
Outdoor
Operation
Range
Cooling
Maximum °C 43 26 43 26
Minimum °C -10 – -10 –
Heating
Maximum °C 24 18 24 18
Minimum °C -15 -16 -15 -16
1. Cooling capacities are based on indoor temperature of 27°C Dry Bulb (80.6°F Dry Bulb), 19.0°C Wet Bulb (66.2°F Wet Bulb) and outdoor air
temperature of 35°C DRY BULB (95°F Dry Bulb), 24°C Wet Bulb (75.2°F Wet Bulb).
2. Heating capacities are based on indoor temperature of 20°C Dry Bulb (68°F Dry Bulb) and outdoor air temperature of 7°C Dry Bulb (44.6°F
Dry Bulb), 6°C Wet Bulb (42.8°F Wet Bulb).
3. Heating low temperature capacity, Input Power and COP measured at 230 V, indoor temperature 20°C, outdoor 2/1°C.
4. Heating extreme low temperature capacity, Input Power and COP measured at 230 V, indoor temperature 20°C, outdoor -7/-8°C.
5. Standby power consumption 10.0w (when switched OFF by remote control, except under self protection control).
6. Specifications are subjected to change without prior notice for further improvement.

Table of Contents

Other manuals for Panasonic CS-Z60UD3EAW

Related product manuals