38
Values of T1, T2, and T3 depend on remote control setting temperature, as shown in below table. After the adjustment of T1, T2
and T3 values, the operation mode for that particular environment and remote control setting is judged and performed, based on the
above operation mode chart, every *(A) minutes.
*(A); Single Type = 30, Multi Type = 180
There is a temperature shifting on T1, T2 and T3 if the operation mode judged is changed from Cooling/Dry to Heating or vice
versa.
Example of operation mode chart adjustment:
From the above table, if remote control setting temperature = 25,
T1 = 25 + 7 = 32; T2 = 25 - 3 = 22; T3 = 25 - 7 = 18
The operation mode chart for this example is as shown in below figure and the operation mode to be performed will depend on
indoor intake air temperature and outdoor air temperature at the time when the judgment is made.
Remote Control Setting Temperature (qC) T1 T2 T3
16 ~ 18 +10 -3 -5
19 ~ 22 +8 -3 -7
23 ~ 26 +7 -3 -7
27 ~ 30 +6 -3 -8
Operation Mode change from Temperature shifts (qC)
Cooling/Dry o Heating -2
Heating o Cooling/Dry +2