12. Servicing Information
Caution:
- Pb free solder has a higher melting point than standard solder; Typically the melting point is
50
(30 - 40°C) higher. Please use a high temperature soldering iron. In case of the soldering
iron
temperature control,please set it to 700 ± 20°F (370 ± 10°C).
- Pb free solder will tend to splash when heated too high (about 1100° F/600°C).
12.1. Troubleshooting
1.
Rated Frequency Operation
During troubleshooting and servicing, rated compressor operating frequency must be obtained
in order to check the specification and technical data. Below are the methods used to obtain
rated compressor operating specification.
(a) Cooling
(i)Press the Auto button continuously for 5 seconds or less than 8 seconds, the air
conditioner
operation at Cooling rated frequency. (“beep will be heard at the 5th second.)
(ii)Short the service terminal (CN-S) of the outdoor printed circuit board. The operation of
air
conditioner is Cooling rated frequency.