ー 23 ー
Display and settings for the communication adaptor board
Various procedures
(04–06) Communication speed
•
Displays the communication speed of the communication adaptor control wiring.
•
The factory setting is 19,200 BPS.
 
•
The following BPS can be selected.
 
1
 19200 BPS ... Intelligent Controller (Do not change from this setting)
 
2
 9600 BPS  ... AMY software
[How to change]
 
1
 Press and hold the SET key for at least 1 second and the BPS value blinks.
 
2
 Press the UP or DOWN key to display 19200 and 9600 alternately.
 
3
 Press and hold the SET key. When the display changes from blinking to lit, the change is completed.
 
4
 It becomes valid after power supply restart of the communication adaptor board.
(04–07) Communication error detection interval
•
Displays the time (minutes) until judging that a communication error with the air conditioner has occurred.
•
The factory setting is 10 minutes.
•
It can be set in the range from 0 to 99 minutes.
•
If it is set to 0 minutes, communication error detection will not be performed.
TGR-318_ENG.indb   23 2017/04/06   10:42:44