1-1-1-1-2
1
Single-Type
1-1. Unit Specications
PZH2
High Static Pressure Ducted Type S-200PE3E5B / U-200PZH2E8
INDOOR MODEL S-200PE3E5B - -
PANEL MODEL - - -
OUTDOOR MODEL - U-200PZH2E8 -
Branch pipe MODEL -
Performance test condition ISO13253 / EN14511 / EN12102 / EN14825
Power supply
Ø, Hz 1Ø 50Hz 3Ø 50Hz
V 220V 230V 240V 380V 400V 415V Min Max
C
O
O
L
I
N
G
Capacity
kW 19.5 19.5 19.5 - - - 5.7 21.0
BTU/h 66500 66500 66500 - - - 19400 71700
Current A 3.40 3.30 3.20 9.00 8.55 8.25 - -
Input power
W 610 610 610 5.450k 5.450k 5.450k - -
TOTAL W - 6.060k 6.060k 6.060k 1.260k 6.800k
Annual consumption TOTAL kWh *
4
- - - - 3030 - - -
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
- - - 3.22 3.22 /A 3.22 4.52 3.09
Erp
*
6
Pdesign kW - - - - 19.5 - - -
η
s,c
(W/W) - - - - 207.0 - - -
Annual consumption
kWh - - - - - - - -
Class - - - - - - - -
Power factor % - - - 92 92 92 - -
Noise indoor
dB-A (H/M/L) 46/44/41 - - -
Power Level dB 78/76/73 - - -
Noise outdoor
dB-A (H/L) - 59/- - -
Power Level dB - 77/- - -
H
E
A
T
I
N
G
Capacity
kW 22.4 22.4 22.4 - - - 5.0 25.0
BTU/h 76400 76400 76400 - - - 17100 85300
Current A 3.40 3.30 3.20 9.25 8.80 8.45 - -
Input power
W 610 610 610 5.600k 5.600k 5.600k - -
TOTAL W - 6.210k 6.210k 6.210k 1.050k 7.900k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
- - - 3.61 3.61 /A 3.61 4.76 3.16
Erp
*
6
Pdesign at -10°C kW - - - - 17.0 - - -
Tbivalent °C - - - - -10 - - -
η
s,h
(W/W) - - - - 141.3 - - -
Annual consumption
kWh - - - - - - - -
elbu(-10°C) kW - - - - 0.00 - - -
Class - - - - - - - -
Power factor % - - - 92 92 92 - -
Noise indoor
dB-A (H/M/L) 46/44/41 - - -
Power Level dB 78/76/73 - - -
Noise outdoor
dB-A (H/L) - 61/- - -
Power Level dB - 79/- - -
EXTRA LOW TEMP
Total capacity(kW)/Input power(W)/COP
- -
Max Current(A) / Max Input power(W) 5.70/1220 5.70/1220 5.60/1220 13.5/8.16k 13.5/8.59k 13.5/8.92k -
Starting current(A) (Cooling/Heating) - - - 9.00/9.25 8.55/8.80 8.25/8.45 -
Comp output(W) - 4.20k 4.20k 4.20k -
Time Delay fuse max size(A) 15 30 -
Network Impedance(ΩMAX.) - - -
Fan motor output (Indoor/Outdoor) W 560 × 2 120 × 2 -
Moisture removal volume
L/h(Pt/h)
5.5 (5.5 ×1) (11.6) - -
External static pressure Pa 75 / (120/180) - -
Indoor
Air ow
Cooling
m
3
/min (m
3
/h) (H/M/L)
72.0/63.0/53.0 (4320)/(3780)/(3180) - - -
Heating
m
3
/min (m
3
/h) (H/M/L)
72.0/63.0/53.0 (4320)/(3780)/(3180) - - -
Outdoor
Air ow
Cooling m
3
/min (m
3
/h) - 164.0 (9840) - -
Heating m
3
/min (m
3
/h) - 164.0 (9840) - -
Refrigerant type / amount
g
(oz) - R32 4.20k (148.2) -
Product dimension
Height
mm(inch)
486 (19-1/8) 1500 (59-1/16) -
Width
mm(inch)
1456 (57-5/16) 980 (38-37/64) -
Depth
mm(inch)
916 (36-1/16) 370 (14-9/16) -
Product dimension (Panel)
H×W×D mm, inch
- - - -
Packing dimension
Height
mm(inch)
610 (24-1/32) 1642 (64-41/64) -
Width
mm(inch)
1646 (60-13/16) 1095 (43-7/64) -
Depth
mm(inch)
1132 (44-9/16) 529 (20-53/64) -
Weight
(NET) k
g
(lb) 86 (190) 117 (258) -
(GROSS)
k
g
(lb) 106 (234) 129 (284) -
Panel (NET)
k
g
(lb) - - - -
Layers limit (actually) 4 (5) 1 (2) -
Operation condition
Cool (DBT) 18°C ~ 32°C -15°C ~ 46°C -
Heat (DBT) 16°C ~ 30°C -20°C ~ 24°C -
Max Working Pressure HP/LP Mpa (bar) 4.15/2.70 (41.5/27.0) -
P
I
P
I
N
G
Pipe diameter mm (inch) (Liquid)Ø9.52(3/8) (Gas)Ø25.4(1) (Liquid)Ø9.52(3/8) (Gas)Ø25.4(1) -
Connecting method (Liquid)ared type (Gas)brazing connection (Liquid)ared type (Gas)brazing connection -
Standard length m(ft) 7.5 (24.6) -
Pipe length range m (ft) 5 ~ 90 m (16.4 ~ 295.3) -
Indoor unit & Outdoor unit height difference m (ft)
30 m(OD located lower) / 30 m(OD located higher) (98.4 / 98.4) -
Add gas amount
g
/m (oz/ft) 60
g
/m (0.645) -
Pipe length for additional gas m (ft) 30m (98.4) -
*1 In case it is necessary to indicate the air ow volume in (l/s), the value in (m³/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2 If the EUROVENT Certied models can be operated under the "extra-low" temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage
230V shall be used.
*3 Network Impedance shall be applicable for EUROPE and CHINA models.
*4 The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 EER and COP classication is at 230V(400V) only in accordance with EU directive 2002/31/EC.
*6 η
s,c
and η
s,h
classication is at 230V(400V) only in accordance with EN-14825. For heating, η
s,h
indicates the value of only Average heating season.
SM830276-00_欧州向け R32シングル TD&SM.indb 2 2019/02/27 11:54:09