1-1-1-1-3
1
Single-Type
1-1. Unit Specications
PZH2
High Static Pressure Ducted Type S-250PE3E5B / U-250PZH2E8
INDOOR MODEL S-250PE3E5B - -
PANEL MODEL - - -
OUTDOOR MODEL - U-250PZH2E8 -
Branch pipe MODEL -
Performance test condition ISO13253 / EN14511 / EN12102 / EN14825
Power supply
Ø, Hz 1Ø 50Hz 3Ø 50Hz
V 220V 230V 240V 380V 400V 415V Min Max
C
O
O
L
I
N
G
Capacity
kW 23.2 23.2 23.2 - - - 6.1 27.0
BTU/h 79200 79200 79200 - - - 20800 92100
Current A 4.30 4.20 4.10 10.8 10.3 9.90 - -
Input power
W 830 830 830 6.630k 6.630k 6.630k - -
TOTAL W - 7.460k 7.460k 7.460k 1.330k 9.200k
Annual consumption TOTAL kWh *
4
- - - - 3730 - - -
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
- - - 3.11 3.11 /B 3.11 4.59 2.93
Erp
*
6
Pdesign kW - - - - 23.2 - - -
η
s,c
(W/W) - - - - 190.6 - - -
Annual consumption
kWh - - - - - - - -
Class - - - - - - - -
Power factor % - - - 93 93 93 - -
Noise indoor
dB-A (H/M/L) 47/45/42 - - -
Power Level dB 79/77/74 - - -
Noise outdoor
dB-A (H/L) - 59/- - -
Power Level dB - 78/- - -
H
E
A
T
I
N
G
Capacity
kW 28.0 28.0 28.0 - - - 5.5 29.0
BTU/h 95500 95500 95500 - - - 18800 98900
Current A 4.30 4.20 4.10 12.0 11.4 11.0 - -
Input power
W 830 830 830 7.380k 7.380k 7.380k - -
TOTAL W - 8.210k 8.210k 8.210k 1.100k 9.500k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
- - - 3.41 3.41 /B 3.41 5.00 3.05
Erp
*
6
Pdesign at -10°C kW - - - - 20.0 - - -
Tbivalent °C - - - - -10 - - -
η
s,h
(W/W) - - - - 142.7 - - -
Annual consumption
kWh - - - - - - - -
elbu(-10°C) kW - - - - 0.00 - - -
Class - - - - - - - -
Power factor % - - - 93 93 93 - -
Noise indoor
dB-A (H/M/L) 47/45/42 - - -
Power Level dB 79/77/74 - - -
Noise outdoor
dB-A (H/L) - 63/- - -
Power Level dB - 82/- - -
EXTRA LOW TEMP
Total capacity(kW)/Input power(W)/COP
- -
Max Current(A) / Max Input power(W) 6.60/1440 6.40/1440 6.30/1440 18.5/11.3k 18.5/11.9k 18.5/12.4k -
Starting current(A) (Cooling/Heating) - - - 10.8/12.0 10.3/11.4 9.90/11.0 -
Comp output(W) - 5.50k 5.50k 5.50k -
Time Delay fuse max size(A) 15 30 -
Network Impedance(ΩMAX.) - - -
Fan motor output (Indoor/Outdoor) W 750 × 2 120 × 2 -
Moisture removal volume
L/h(Pt/h)
6.8 (6.8 ×1) (14.3) - -
External static pressure Pa 75 / (130/200) - -
Indoor
Air ow
Cooling
m
3
/min (m
3
/h) (H/M/L)
84.0/72.0/59.0 (5040)/(4320)/(3450) - - -
Heating
m
3
/min (m
3
/h) (H/M/L)
84.0/72.0/59.0 (5040)/(4320)/(3450) - - -
Outdoor
Air ow
Cooling m
3
/min (m
3
/h) - 160.0 (9600) - -
Heating m
3
/min (m
3
/h) - 160.0 (9600) - -
Refrigerant type / amount
g
(oz) - R32 5.20k (183.4) -
Product dimension
Height
mm(inch)
486 (19-1/8) 1500 (59-1/16) -
Width
mm(inch)
1456 (57-5/16) 980 (38-37/64) -
Depth
mm(inch)
916 (36-1/16) 370 (14-9/16) -
Product dimension (Panel)
H×W×D mm, inch
- - - -
Packing dimension
Height
mm(inch)
610 (24-1/32) 1642 (64-41/64) -
Width
mm(inch)
1646 (60-13/16) 1095 (43-7/64) -
Depth
mm(inch)
1132 (44-9/16) 529 (20-53/64) -
Weight
(NET) k
g
(lb) 88 (195) 128 (282) -
(GROSS)
k
g
(lb) 108 (239) 140 (309) -
Panel (NET)
k
g
(lb) - - - -
Layers limit (actually) 4 (5) 1 (2) -
Operation condition
Cool (DBT) 18°C ~ 32°C -15°C ~ 46°C -
Heat (DBT) 16°C ~ 30°C -20°C ~ 24°C -
Max Working Pressure HP/LP Mpa (bar) 4.15/2.70 (41.5/27.0) -
P
I
P
I
N
G
Pipe diameter mm (inch) (Liquid)Ø12.7(1/2) (Gas)Ø25.4(1) (Liquid)Ø12.7(1/2) (Gas)Ø25.4(1) -
Connecting method (Liquid)ared type (Gas)brazing connection (Liquid)ared type (Gas)brazing connection -
Standard length m(ft) 7.5 (24.6) -
Pipe length range m (ft) 5 ~ 60 m (16.4 ~ 196.9) -
Indoor unit & Outdoor unit height difference m (ft)
30 m(OD located lower) / 30 m(OD located higher) (98.4 / 98.4) -
Add gas amount
g
/m (oz/ft) 80
g
/m (0.860) -
Pipe length for additional gas m (ft) 30m (98.4) -
*1 In case it is necessary to indicate the air ow volume in (l/s), the value in (m³/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2 If the EUROVENT Certied models can be operated under the "extra-low" temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage
230V shall be used.
*3 Network Impedance shall be applicable for EUROPE and CHINA models.
*4 The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 EER and COP classication is at 230V(400V) only in accordance with EU directive 2002/31/EC.
*6 η
s,c
and η
s,h
classication is at 230V(400V) only in accordance with EN-14825. For heating, η
s,h
indicates the value of only Average heating season.
SM830276-00_欧州向け R32シングル TD&SM.indb 3 2019/02/27 11:54:09