Precautions Concerning Programs
4-14
Example 2: Using the CT instruction between JP and LBL instructions
LBL 1
R0
JP 1
X0
X1
200CT
R0
X0
Final timing at
which the
previous JP
instruction was
not executed
The count is not incremented, because
the final timing at which the previous JP
instruction was not executed has not
been changed, and the execution
condition X0 for the counter input has
not changed.
R0
X0
Counting
operation
Time chart 2
Final timing at
which the
previous JP
instruction
was not
executed
The count is incremented, because the
count input changed from off to on after the
final timing at which the previous JP
instruction was not executed.