4.4 Operation Errors
4-15
4.4 Operation Errors
4.4.1 Operation Errors
An operation error is a condition in which operation is impossible when a high-level
instruction is executed.
When an operation error occurs, the ERROR LED will light (for FP0, ERROR/ALARM
LED will blink), and the operation error flags (R9007 and R9008) will turn on.
The operation error code K45 (H2D) is set at special data register DT9000/DT90000.
The error address is stored in special data registers DT9017 and DT9018/DT90017 and
DT90018.
− With the FP0 C10, C14, C16, C32/FP−e, the self−diagnosis error codes are
stored in DT9000, and addresses at which errors occurred are stored in
DT9017 and DT9018.
− With the FP0R/FP0 T32C/FPΣ/FP−X/FP2/FP2SH/FP10SH, the self−diagnosis
error codes are stored in DT90000, and addresses at which errors occurred
are stored in DT90017 and DT90018.
Types of operation error
Address error
The memory address (number) specified by index modification is outside the area which
can be used
BCD data error
Operation is attempted on non−BCD data when an instruction handling BCD data is
executed, or BCD conversion is attempted on data which is not within the possible
conversion range.
Parameter error
In an instruction requiring the specification of control data, the specified data is outside
the possible range.
Over area error
The data manipulated by a block instruction exceeds the memory range.