Precautions Concerning Programs
4-16
4.4.2 Operation Mode when an Operation Error Occurs
Normally, the operation stops when an operation error occurs.
However, when you set system register 26 to “continuation” (K1), the CPU operates
even if an operation error occurs.
System registers are specified as described below.
Using programming tool software
1. Set the mode of the CPU to PROG.
2. Select the “Option” in “PLC Configuration” option from the menu.
3. On the “PLC Configuration” menu, select “Action on error”. This
displays system registers 20 to 28.
4. The check of system register 26 is removed.
5. Press the “OK” to write the setting to the PLC.
Using FP programmer II Ver. 2
1. Set the mode of the CPU to PROG.
2. Press the keys on the FP programmer II, as shown below.
ENTACLR
OP
(−)
5 0
3. Specify the register number (26) for the parameter to be set and read
the parameter.
The value set in the selected system register 26 will be displayed.
2 6
READ
4. To change a set value, press the (HELP) “CLR” key and write the K1
parameter.