Precautions Concerning Programs
4-34
4.10 Second Program Area (FP2SH, FP10SH)
Explanation of operation method for FP2SH and FP10SH
For the type of FP2SH of which program capacity exceeds 60k steps and for the type
of FP10SH of which program capacity exceeds 60k steps if the memory is added, the
program area is divided into the first program area and the second program area. The
divided programs are separate program units, however, uploading and downloading
with TOOL is performed simultaneously. There are following restrictions for the
operation devices.
Device and function First program Second program
Bits X, Y, R, LWords WX, WY, WR,
WL, DT, Ld, In, Fl
Common device
SALL Subroutine call The subroutine of the second pro-
gram cannot be called up.
The subroutine of the first program
cannot be called up.
SUB Subroutine entry 100 100
JP Jump 255 (However, jumping to the second
program is not possible.)
255 (However, jumping to the first
program is not possible.)
LBL Label 255 255
INT Interrupt program Can be written in the first program
only.
Cannot be used.
SSTP Step ladder Can be written in the first program
only.
Cannot be used.
MC, MCE Master control 255 (A pair must be formed in the first
program.)
255 (A pair must be formed in the
second program.)
Syntax check
− For SUB, JP, LBL, MC and MCE, the checks are performed as the above
table.
− The duplicated output of OT and KP instructions and the duplicated use of
timer and counter instructions are checked throughout the first and second
programs.