5-145
FP-X (A: Available, N/A: Not available)
Address Name Description
Read-
ing
Writ-
ing
DT90300 Lower words A A
Note)
DT90301
Elapsed
value
area
Higher words
Counting area for input (X0) or
(X0, X1) of the main unit.
A A
Note)
DT90302 Lower words A A
Note)
DT90303
Target
value
area
Higher words
HSC-CH0
The target value is set when
instructions F166 (HC1S) and
F167 (HC1R) are executed.
A A
Note)
DT90304 Lower words A A
Note)
DT90305
Elapsed
value
area
Higher words
Counting area for input (X1) of
the main unit.
A A
Note)
DT90306 Lower words A A
Note)
DT90307
Target
value
area
Higher words
HSC-CH1
The target value is set when
instructions F166 (HC1S) and
F167 (HC1R) are executed.
A A
Note)
DT90308 Lower words A A
Note)
DT90309
Elapsed
value
area
Higher words
Counting area for input (X2) or
(X2, X3) of the main unit.
A A
Note)
DT90310 Lower words A A
Note)
DT90311
Target
value
area
Higher words
HSC-CH2
The target value is set when
instructions F166 (HC1S) and
F167 (HC1R) are executed.
A A
Note)
DT90312 Lower words A A
Note)
DT90313
Elapsed
value
area
Higher words
Counting area for input (X3) of
the main unit.
A A
Note)
DT90314 Lower words A A
Note)
DT90315
Target
value
area
Higher words
HSC-CH3
The target value is set when
instructions F166 (HC1S) and
F167 (HC1R) are executed.
A A
Note)
DT90316 Lower words A A
Note)
DT90317
Elapsed
value
area
Higher words
Counting area for input (X4) or
(X4, X5) of the main unit.
A A
Note)
DT90318 Lower words A A
Note)
DT90319
Target
value
area
Higher words
HSC-CH4
The target value is set when
instructions F166 (HC1S) and
F167 (HC1R) are executed.
A A
Note)
Note) Writing in the elapsed value area is available by F1 (DMV) instruction only.