5-165
5.1.17 Table of Special Internal Relays for FP1/FP-M/FP2/FP2SH/FP10SH/FP3
FP1/FP-M/FP2/FP2SH/FP10SH/FP3
Address Name Description
R9000
Self-diagnostic error
flag
(Available PLC: All
types)
Turns on when a self-diagnostic error occurs.
The self-diagnostic error code is stored in:
- FP1/FP-M/FP3: DT9000
- FP2/FP2SH/FP10SH: DT90000
R9001 Not used -
MEWNET-TR master
error flag
(Available PLC: FP3/
FP10SH)
Turns on when a communication error occurs in the
MEWNET-TR master unit or MEWNET-TR network. The
slot, where the erroneous MEWNET-TR master unit is
installed, can be checked using:
- FP3: DT9002 and DT9003
- FP10SH: DT90002, DT90003
R9002
I/O error flag
(Available PLC: FP2/
FP2SH)
Turns on when the error occurs in the I/O unit. The slot
number of the unit where the error was occurred is stored in
DT90002, DT90003.
R9003
Intelligent unit error
flag
Turns on when an error occurs in an intelligent unit. The slot
number, where the erroneous intelligent unit is installed is
stored in:
- FP3: DT9006 and DT9007
- FP2/FP2SH/FP10SH: DT90006, DT90007
R9004
I/O verification error
flag
Turns on when an I/O verification error occurs.
The slot number of the I/O unit where the verification error
was occurred is stored in:
- FP3: DT9010 and DT9011
-FP2/FP2SH/FP10SH: DT90010, DT90011
R9005
Backup battery error
flag (non-hold)
(Available PLC: FP-M
C20, C32/FP1 C24,
C40, C56, C72/FP2/
FP2SH/FP3/FP10SH)
Turns on for an instant when a backup battery error occurs.
R9006
Backup battery error
flag (hold)
(Available PLC: FP-M
C20, C32/FP1 C24,
C40, C56, C72/FP2/
FP2SH/FP3/FP10SH)
Turns on and keeps the on state when a backup battery
error occurs. To reset R9006,
- turn the power to off and then turn it on,
- initialize, after removing the cause of error.
R9007
Operation error flag
(hold)
Turns on and keeps the on state when an operation error
occurs. The address where the error occurred is stored in:
- FP1/FP-M/FP3: DT9017
– FP2/FP2SH/FP10SH: DT90017
(Indicates the first operation error which occurred).
R9008
Operation error flag
(non-hold)
(Available PLC:
FP1/FP-M/FP2/FP2SH/
FP10SH)
Turns on for an instant when an operation error occurs. The
address where the operation error occurred is stored in:
- FP1/FP-M/FP3: DT9018
-FP2/FP2SH/FP10SH: DT90018
The contents change each time a new error occurs.