5-166
FP1/FP-M/FP2/FP2SH/FP10SH/FP3
Address Name Description
R9009 Carry flag
Turns on for an instant,
- when an overflow or underflow occurs.
- when “1” is set by one of the shift instructions.
R900A > Flag
Turns on for an instant when the compared results become
larger in the “F60 (CMP)/P60 (PCMP),
F61(DCMP)P61(PDCMP),F62 (WIN)/P62 (PWIN) or F63
(DWIN)/P63 (PDWIN) comparison instructions.”
R900B = Flag
Turns on for an instant,
- when the compared results are equal in the comparison
instructions.
- when the calculated results become 0 in the arithmetic
instructions.
R900C < Flag
Turns on for an instant when the compared results become
smaller in the “F60 (CMP)/P60 (PCMP),
F61(DCMP)P61(PDCMP), F62 (WIN)/P62 ,(PWIN) or F63
(DWIN)/P63 (PDWIN) comparison instructions.”
R900D
Auxiliary timer
contact
(Available PLC: FP-M
C20, C32/FP1 C56,
C72/FP2/FP2SH/FP3/
FP10SH)
Turns on when the set time elapses (set value reaches 0) in
the timing operation of the F137(STMR)/F183(DSTM)
auxiliary timer instruction.
Available PLC for F183 (DSTM) instruction: FP2/FP2SH/
FP10SH
The R900D turns off when the trigger for auxiliary timer
instruction turns off.
R900E
Tool port error flag
(Available PLC: FP1/
FP-M/FP2SH/FP10SH)
Turns on when communication error at tool port is occurred.
R900F
Constant scan error
flag
Turns on when the scan time exceeds the time specified in
system register 34 during constant scan execution.
R9010 Always on relay Always on.
R9011 Always off relay Always off.
R9012 Scan pulse relay Turns on and off alternately at each scan.
R9013 Initial on pulse relay
Turns on only at the first scan in the operation.
Turns off from the second scan and maintains the off state.
R9014 Initial off pulse relay
Turns off only at the first scan in the operation.
Turns on from the second scan andmaintains the on state.
R9015
Step ladder initial on
pulse relay
Turns on for an instant only in the first scan of the process
the moment step ladder process is opened.
R9016,
R9017
Not used
-
R9018
0.01 s clock pulse
relay
Repeats on/off operations in 0.01 s cycles.
R9019
0.02 s clock pulse
relay
Repeats on/off operations in 0.02 s cycles.
R901A 0.1 s clock pulse relay Repeats on/off operations in 0.1 s cycles.
R901B 0.2 s clock pulse relay Repeats on/off operations in 0.2 s cycles.
R901C 1 s clock pulse relay Repeats on/off operations in 1 s cycles.