5-167
FP1/FP-M/FP2/FP2SH/FP10SH/FP3
Address Name Description
R901D 2 s clock pulse relay Repeats on/off operations in 2 s cycles.
R901E
1 min clock pulse
relay
Repeats on/off operations in 1 min cycles.
R901F Not used -
R9020 RUN mode flag
Turns off while the mode selector is set to PROG.
Turns on while the mode selector is set to RUN.
R9021
Test RUN mode flag
(Available PLC: FP2/
FP2SH/FP3/FP10SH)
Turns on while the initialize/test switch of the CPU is set to
TEST and mode selector is set to RUN. (test run operation
start)
Turns off during the normal RUN mode.
R9022
Break flag
(Available PLC: FP2/
FP2SH/FP3/FP10SH)
Turns on while the BRK instruction is executing or the step
run is executing.
R9023
Break enable flag
(Available PLC: FP2/
FP2SH/FP3/FP10SH)
Turns on while the BRK instruction is enabled in the test
RUN mode.
R9024
Output update enable
flag in the test RUN
mode
(Available PLC: FP2/
FP2SH/FP3/FP10SH)
Turns on while the output update is enabled in the test RUN
mode.
R9025
Single instruction flag
(Available PLC: FP2/
FP2SH/FP3/FP10SH)
Turns on while the single instruction execution is selected in
the test RUN mode.
R9026
Message flag
(Available PLC: FP-M
C20, C32/FP1 C24,
C40, C56, C72/FP2/
FP2SH/FP3/FP10SH)
Turns on while the F149 (MSG)/P149 (PMSG) instruction is
executed.
R9027 Remote mode flag Turns on while the mode selector is set to REMOTE.
R9028
Break clear flag
(Available PLC: FP2/
FP2SH/FP3/FP10SH)
Turns on when the break operation is cleared.
R9029 Forcing flag
Turns on during forced on/off operation for I/O relay and
timer/counter contacts.
External interrupt
enable flag
(Available PLC: FP-
M/FP1 C24, C40, C56,
C72/FP2/FP2SH/FP3/
FP10SH)
Turns on while the external interrupt trigger is enabled by
the ICTL instruction.
R902A
Interrupt flag
(Available PLC: FP2)
Turns on while the periodical interrupt is executed by the
ICTL instruction.
R902B
Interrupt error flag
(Available PLC:
FP-M/FP1 C24, C40,
C56, C72/FP2/FP2SH/
FP3/FP10SH)
Turns on when an interrupt error occurs.
R902C Sampling point flag
Turns off during instructed sampling.
Turns on while sampling is triggered by the periodical
interrupt.