5-169
FP1/FP-M/FP2/FP2SH/FP10SH/FP3
Address Name Description
F152 (RMRD)/P152
(PRMRD) and F153
(RMWT)/P153
(PRMWT) instruction
end flag
(Available PLC: FP2/
FP2SH/FP3/FP10SH)
Monitors if an abnormality has been detected during the
execution of the F152 (RMRD)/P152 (PRMRD) and F153
(RMWT)/P153 (PRMWT) instructions as follows:
- off: No abnormality detected.
- on: An abnormality detected. (access error)
The error code is stored in:
- FP3: DT9036
- FP2/FP2SH/FP10SH: DT90036
R9036
I/O link error flag
(Available PLC: FP-M
C20, C23/FP1)
Turns on when the erroro occurs using the I/O link function.
R9037
COM port communica-
tion error flag
(Available PLC:
FP-M C20C, C32C/FP1
C24C, C40C, C56C,
C72C/FP2/FP2SH/
FP10SH)
Turns on when the serial data communication error occurs
using COM port.
Turns off when data is being sent by the F144 (TRNS)
instruction.
R9038
COM port receive flag
(Available PLC:
FP-M C20C, C32C/FP1
C24C, C40C, C56C,
C72C/FP2/FP2SH/
FP10SH)
Turns on when the end code is received during the serial
data communicating.
R9039
COM port send flag
(Available PLC:
FP-M C20C, C32C/FP1
C24C, C40C, C56C,
C72C/FP2/FP2SH/
FP10SH)
Turns on while data is not send during the serial data
communicating.
Turns off while data is being sent during the serial data
communicating.
R903A
High-speed counter
control flag (ch0)
(Available PLC: FP-M
C20, C32/FP1)
Turns on while the high-speed counter instructions
F166(HC1S) to F170(PWM) are executed.
Cam control flag
(Available PLC: FP-M/
FP1)
Turns on while the cam control instruction F165 (CAMO) is
executed.
R903B
High-speed counter
control flag (ch1)
Turns on while the high-speed counter instructions
F166(HC1S) to F170(PWM) are executed.
R903C
High-speed counter
control flag (ch2)
Turns on while the high-speed counter instructions
F166(HC1S) to F170(PWM) are executed.
R903D
High-speed counter
control flag (ch3)
Turns on while the high-speed counter instructions
F166(HC1S) to F170(PWM) are executed.
R903E Not used -
R903F Not used -
R9040 Error alarm (0 to 2047)
Turns on while the error alarm relay (E0 to E2047) acts.
Turns off when the all error alarm relay turns off.