Basic Instructions
2 134
System registers
No. Name Setting value and range
40
Range of link relays used 0 to 64 words
41
Range of link data registers used 0 to 128 words
42
Starting number for link relay
transmission
0to63
PLC
43
Link relay transmission size 0 to 64 words
PLC
WO0
44
Starting number for link data register
transmission
0 to 127
45
Link data register transmission size 0 to 127 words
46
PC (PLC) Link switch flag Normal/reverse
47
Maximum unit number setting for
MEWNETW0 PLC link
1to16
50
Range of link relays used 0 to 64 words
51
Range of link data registers used 0 to 128 words
52
Starting number for link relay
transmission
64 to 127
PLC
WO 1
53
Link relay transmission size 0 to 64 words
WO1
54
Starting number for link data register
transmission
128 to 255
55
Link data register transmission size 0 to 127 words
57
Maximum unit number setting for
MEWNETW0 PLC link
1to16
Program example
F0 MV , K 64, DT0
F0 MV , K 128, DT1
F0 MV , K 0, DT2
F0 MV , K 10, DT3
F0 MV , K 0, DT4
F0 MV , K 10, DT5
F0 MV , K 0, DT6
F0 MV , K 5, DT7
Set value of system register 40
SYS2 , DT0, K40, K47
Set value of system register 42
Set value of system register 41
Set value of system register 43
Set value of system register 44
Set value of system register 45
Set value of system register 46
Set value of system register 47
Sets the values stored in DT0 to DT7 in system
registers 40 to 47
Decimals of the average value are rounded off so that the average value is an integer.