High−level Instructions
3 − 327
Preparation of transmission
1) Setting the transmission format
For FP10SH
The initial settings for the transmission format are as follows:
− Data length: 8 bits
− Parity check: Yes, odd
− Stop bits: 1 bit
− End code: C
R
− Start code: No STX
To change the transmission format to match the external device connected to the COM. port, set the
parameters with the upper row of operation mode switches.
Upper dip switches
Lower dip switches
Operation mode switches (using upper dip switch)
off
on
off
on
Functions
Settings
SW1 SW2 SW3 SW4 SW5 SW6 SW7 SW8
MODEM
tl
Disabled off
control
Enabled on
Start code
STX (H02)
invalid
off
STX (H02) valid on
End code
None off off
C
R
(H0D) and LF
(H0A)
on off
C
R
(H0D) off on
EXT (H03) on on
Stop bit
2 bits off
p
1 bit on
Parity check
Invalid off off
y
Even parity on off
Odd parity on on
Data length
(character
7 bits off
(
c
h
aracter
bit)
8 bits on
For FP2/FP2SH
Set the transmission format parameter so that the ”Transmission Format Setting” of system register 413
matches the external device connected to the COM. port. The default setting is the same as that of the
FP10SH.
The selected end code is automatically added during transmission. To disable the end code, set the number
of transmission bytes using a negative value before the F144 (TRNS) instruction.
If the start code is set to “STX valid”, STX will be automatically added.
FP2/FP2SH/FP10SH