High−level Instructions
3 − 338
For information on the contents of error codes, refer to the manual. If the error code is H73, a communication
time−out error has occurred.
The time−out time can be changed within a range of 10.0 ms to 81.9 seconds (in units of 2.5 ms), using the
setting of system register 32.
The default value is set to 10 seconds.
Error code (HEX) Description
73 Time−out: Waiting for response
For global transmission (the transmission performed by specifying H00 for the unit No.), the program
should be set up so that the transmission is executed after a time of at least the maximum scan time
elapsed.
The F145 or F146 instruction cannot be executed if the target is a special internal relay (from R9000)
or a special data register (from DT9000) or file register FL.
FPΣ/FP−X/FP0R