High−level Instructions
3 − 350
Outline Sends data to another station through link modules in the network.
Program example
Ladder
Diagram
Boolean
Ladder Diagram
Address Instruction
10
F145 SEND, DT10 , DT20 , DT 0 , K 100
S1
S2
Trigger
R0
D
N
10
11
ST R 0
F145 (SEND)
DT 10
DT 20
DT 0
K 100
S1 Starting 16-bit area for storing control data
S2 Starting 16-bit area for storing source data (data area at the local station)
D T ype of destination operands for storing data in the remote station. Be sure to
select the area by setting address 0 (destination data area at another station).
N Starting 16-bit area address for the destination operand specified in D above
(destination data area in another station).
Operands
O
p
erand
Relay Timer/Counter Register
Index
register
Constant
Index
modifier
Operand
WX WY WR WL SV EV DT LD FL IX IY K H
modifier
S1 A A A A A A A A A N/A N/A N/A N/A A
S2 A A A A A A A A A N/A N/A N/A N/A A
D N/A A A A A A A A A N/A N/A N/A N/A N/A
N N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A A A A
Explanation of example
1
Example of word unit transmission
When the control data is as follows:
Word unit 5 words
Unit No.10
Route No.1
DT10(S1)=H0005 (=K5)
DT11(S1+1)=H01
0A
the 5 words of data from DT20 to DT24 are sent to DT100 to DT104 of unit No. 10, which is
connected to route No. 1, when the execution condition (trigger) R0 turns on.
F145
P145
(PSEND)
(SEND)
Data send (MEWNET link)