High−level Instructions
3 − 351
2
Example of bit unit transmission
When the control data is as follows:
Bit unit Bit No. 13 of local station
Unit No.10
Route No.1
Bit No. 5 of remote station
DT10(S1)=H850D
DT11(S1+1)=H0
10A
the on and off information of Bit No. 13 of DT20 is sent to Bit No. 5 of DT100 of Unit No. 10, which is
connected to route No. 1, when the execution condition (trigger) R0 turns on.
If the network is configured only of the FP2, FP2SH, and FP10SH, specifying [FF] (HFF) for the unit number
sends the same contents to all of the link stations on the same network.
Description
This sends the local station data for the area specified by S2 to the areas specified by the D and N of the
remote stations connected with the MEWNET−W, MEWNET−P, and MEWNET−H.
The remote stations (routes and unit numbers), the transmission unit (bit unit or word unit), the transmission
method, and other parameters are specified by the control data S1.
Link unit
CPU
Local
station
Remote
station
S2 D N
F145 (SEND) execution
The remote station is specified by S1.
If general−purpose communication through the COM. port of the FP2, FP2SH, and FP10SH is being used,
F144 (TRNS) instruction is used instead of this instruction.
Refer to the section describing the F144 (TRNS) instruction.