High−level Instructions
3 − 382
(1) Specifying word unit reception
If word unit reception is being used, the data for the specified number of words is sent from the memory area
of the remote station specified by S2 and N, and is stored in the memory area of the local station beginning
with D. If only the MEWNET−H network is being used, up to 1,020 words can be received at one time, and if
the network is using the MEWNET−P and MEWNET−W, up to 16 words can be received at one time.
15
Number of words received : H001 to H3FC (1 to 1020)
Specifies H0.
S1:
11 7 4 0
Example: If 10 words of data are being received, K10(H000A) should be
specified in S1.
(2) Specifying bit unit reception
When data is being sent in bit units, the information for the specified bit of the memory area of the remote
station specified by S2 and N is stored in the specified bit of the memory area of the local station specified by
D.
15
Bit No. of remote station’s memory area: H0 to HF(0 to 15)
Specifies H8.
S1:
11 7 4 0
Specifies H0
Bit No. of local station’s memory area: H0 to HF(0 to 15)
Example: If the data from Bit No. 0 of the memory area in the remote station
is being sent to Bit 15 of the local station memory area, H8F00
should be specified in S1.
(3) Specifying the remote station (common to both word/bit transmission)
1
Specifying the route No. and depth
Depth of remote station: H01 to H03
Specifies H8.
S1+1:
Route No. of local station: H1 to H8