High−level Instructions
3 − 474
Possible specification range for “Yn”: Devices specified for the match ON/OFF output
Type
Device area
FP0R Y0 to Y1F
Example of target value match OFF setting
When specifying the high−speed counter
Condition
(1) Specify the high−speed counter channle number 0.
(2) Set the target value to 10000.
(3) Set the output coil to be turned off when the values match to Y2.
(DF)
F167 HC1R, H0, K10000, Y2
R0
High−speed counter control start
Execution of program
10000
0
R0
R9110
Y2
Targe value match OFF
The number of the high−speed counter control flag varies
depending on the channel used.
Regarding the channel number and control flag for each
model, refer to the table on the next page.
End of F166 control (clear)
Elapsed value
Target value
Control flag
FP0R
However, for the device that is not implemented, only the memory turns ON/OFF.