High−level Instructions
3 − 492
Data table settings
S Control code
H0 to H16 (*1)
S+1 Duty (%) K1 to K999 (0.1% to 99.9%)
(*1): Control code contents (frequency settings)
FP0 FP0 compatibility mode of FP0R
Setting Frequency (Hz) Period (ms) Frequency (Hz) Period (ms)
H11 1000 1.0 1000 1.0
H12 714 1.4 750 1.3
H13 500 2.0 500 2.0
H14 400 2.5 400 2.5
H15 200 5.0 200 5.0
H16 100 10.0 100 10.0
H0 38 26.3 40 25.0
H1 19 52.6 20 50.0
H2 9.5 105.3 10 100.0
H3 4.8 208.3 6 166.7
H4 2.4 416.7 Cannot be specified
H5 1.2 833.3 Cannot be specified
H6 0.6 1666.7 Cannot be specified
H7 0.3 3333.3 Cannot be specified
H8 0.15 6666.7 Cannot be specified
H11 to H16 are supported by CPU Ver. 2.0 and subsequent versions.
Flag conditions
・Error flag (R9007): Turns on and stays on when:
・Error flag (R9008): Turns on for an instant when:
− The area specified using the index modifier exceeds the limit.
− n is number except 0 and 1.
− The frequency setting value set with (S) is outside the specification range.
− 100% or higher is set with (S + 1)
FP0/FP−e