High−level Instructions
3 − 528
Absolute <Absolute value control>
The pulse that is the difference between the specified target value and the current value is output.
Mode selection
Target value
CW/CCW
PLS+SIGN
Forward OFF
Reverse ON
PLS+SIGN
Forward ON
Reverse OFF
Elapsed value
When target value is
larger than current
value
Output from CW
Pulse output when
direction output is off
Pulse output when
direction output is on
Addition
When target value is
smaller than current
value
Output from CCW
Pulse output when
direction output is on
Pulse output when
direction output is off
Subtraction
[Explanation of pulse output operation]
Pulses are output using a duty of 25% fixedly.
When using the PLS +SIGN method, pulses will be output approx. 300 us later after the output of direction
signal. (The characteristics of a motor driver is considered.)
Method of acceleration/deceleration and initial speed
When the deceleration stop is requested during acceleration, deceleration is performed with the same slope
of the deceleration time from the target speed.
In this instruction, the operation is processed giving the acceleration/deceleration time priority.
The initial speed may be corrected to enable accelerating/decelerating within the specified time.
Sample program
F1 DMV, H10000000, DT0
F1 DMV, K1000, DT2
F1 DMV, K25000, DT4
F1 DMV, K300, DT6
F1 DMV, K450, DT8
R0
F172 PLSH, DT0, K0
R1
150ms 225ms
300ms 450ms
1kHz
25kHz
50kHz
Pulse
output
instruction
flag
Flag
Flag conditions
・Error flag (R9007):
・Error flag (R9008):
− Turns on when the control code or frequency is out of the settable range
(when the instruction is started).
− Turns on when the area specified using the index modifier exceeds the limit.
− Turns on when n is out of the specified range.
− Turns on when the pulse output of the specified channel is not set by the
system register.